The Fenwal 35-63J101-011 Ignition Control Board replaces the following Johnson Ignition Controls.
G770KGA-1, G770KGA-2, G770KGA-3, G770KHA-2
APPLICATIONS
The Fenwal 35-63J series Intermittent Pilot Ignition Control (35- 63J) is a microprocessor based ignition control suitable for replacing many existing intermittent pilot ignition controls from various manufacturers.
The 35-63J is a direct form, fit, and functional replacement for the discontinued Johnson G77x Series controls. The 35-63J is available in a number of timing configurations that match popular G77x applications. This provides a much better solution than a universal type aftermarket control.
The 35-63J is suitable for many types of heating applications including commercial cooking, furnaces and boilers. It is also great for water heaters that require intermittent pilot ignition, burner supervision through flame rectification, and safety shutoff. It can be used with with Natural, LP, and the mixed gases that are used in gas-fired appliances.
The microprocessor circuit design of the 35-63J provides precise, repeatable timing and operating sequences. High-energy spark output and excellent flame sense characteristics provide reliable burner operation. The on-board diagnostics with LED output make troubleshooting easy and ensure safe and efficient operation.
FEATURES - Safe start and full-time flame sensing - Wide variety of prepurge and interpurge timings - Single or three trials for ignition - Diagnostic LED with Fenwal error codes - Three ground terminals for ease of wiring - Remote or local flame sense options - Automatic 5 min or 1 hour reset after lockout options.
SPECIFICATIONS Input Power | Control: 18-30 VAC 50/60 Hz (Class 2 Transformer) | Input Current Drain | 300 mA @24 VAC with gas and pilot relays energized (Control only) | Main Gas Valve | 2.0A max (continuous) | Pilot Gas Valve | 2.0A max (continuous) | Operating Temperature | -40 to +176 deg. F (-40 to +80 deg. C) | Sforage Temperature | -40 deg. F to +185 deg. F (-40 deg. C to +85 deg. C) | Flame Sensitivity | 0.3 uA minimum | Flame Failure Response or Re-ignition Time | 0.8 seconds maximum | Flame Detecfor Self-check Rate | Once per second minimum | Types of Gas | Natural, LP, or manufactured | Spark Rate | Remote sense (50/60 Hz) Local sense (25/30 Hz) | Size (LxWXH) | 4.92 x 3.32 x 2.71 inches (with cover) 12.50 x 8.43 x 6.88 cm (with cover) | Weight | 8 ounces (nominal) 224 grams (nominal) | Moisture Resistance | Conformal coated to operate to 95% R.H. (non-condensing) | Tries for Ignition | One or three try versions available | Trial for Ignition Periods | 8, 25, 50, 85, 120 seconds available | Prepurge Timings | None, 4, 15, or 30 seconds available | Interpurge Timings | None, 15, 30, or 45 seconds available | CONTROL CONFIGURATION | Options | Recycle After Loss of Flame (standard) | Enclosure | Noryl Gray Enclosure | Tries for Ignition, Flame Sense and Lockout Reset Methods | Single Try, Remote Sense Thermostat / power off reset | Pre-Purge | None | Inter-Purge | 15 Seconds | Trial for Ignition | 8 Seconds
|
|
|
|
|
|
|
|